These luminaires are used indoors (ta 40 C) where emergency light is needed. Each luminaire must be permanently connected to mains power supply.
-
In normal operation the led strip lights and the battery is charging.
-
In case of a mains power supply failure the luminaire will light the led strip automatically in emergency mode.
-
When the mains power supply is restored, the device turns to normal operation.
-
After installation, 24 hours charging cycle must be completed, in order to achieve the nominal autonomy.
-
During commissioning of the luminaire write the commissioning date on the battery.
-
When power is applied to the unit inspect that the CHARGE indicator is steady, and that the led lamp is lit (maintained operation) or OFF (non-maintained operation)
-
A full duration test should be conducted after 24 hours of continuous charging. The test is initiated by isolating the mains power supply.
-
Verify that the LED lamp is lit during the test period for at least the stated duration.